GETTING STARTED MANUAL REVISION 2.0
12
Keypad Display Screens
To reach the Main Menu press the Menu button after powering up. Based on the highlighted menu option when the
enter key () is pressed will bring up one of the following screens.
Menu Key
Pressing the ‘Menu’ key shows the following:
ACTUAL DISPLAY DESCRIPTION
Status
Selecting the ‘Status’ menu option shows the following Chiller Status screen:
ACTUAL DISPLAY DESCRIPTION
Pressing the Page Down button shows the following Circuit Status screen:
ACTUAL DISPLAY DESCRIPTION
Pressing the Page Down button shows the next Circuit Status screen:
ACTUAL DISPLAY DESCRIPTION
09:56 Main Menu
-Status -Setpoints
-Outputs -Serv Tools
-Inputs -Lckout RST
-Alarms -Lckout ALM
-Graphs -Passwords
Help
HH:MM Screen Title
-Control Status Display -Active Setpoints Display
-Relay/Analog Display -Service Tools Display
-Sensor Input Display -Lockout Reset Display
-Alarm Display -Lockout Alarm Display
-Graphing Display -Password Display
Help
09:56 Unit 23/35
UNIT IS LOADED
002:26:18
WTD ACT WTD% DLY ROC
1 1 100% 300 0.0
TARG=27.0
PG PG
HH:MM CHILLER UNIT LEV/ENT
CURRENT CONTROL STATE
TIME IN CURRENT STATE
WANTED ACTUAL WANTED% DELAY SLOPE
#STEPS #STEPS ACTUAL% NEXT CHG DIRECTION
TARGET SET POINT + TARGET RESET
Page Up Page Down
09:56 CMP #1 23/35
CMP IS HOLDING
002:26:18
SUCT DISC OPD MOTOR
44P 222P 156P 101%
33F 177F OK OK
PG PG
HH:MM CIRCUIT LEV/ENT
CURRENT CONTROL STATE
TIME IN CURRENT STATE
SUCTION DISCHARGE OIL DIFFERENTIAL MOTOR
PRESSURE PRESSURE PRESSURE AMP %
TEMPERATURE TEMPERATURE STATUS STATUS
Page Up Page Down
09:55 CMP #1 45/54
CMP OFF/READY
000:00:42
SST SSH SCT DSH
38 16.9 97 79.2
PG PG
HH:MM CIRCUIT LEV/ENT
CURRENT CONTROL STATE
TIME IN CURRENT STATE
SAT.SUCT. SUCT SHEAT SAT.COND. DISC SHEAT
TEMP TEMP TEMP TEMP
Page Up Page Down