MAGNUM VERSION 8 MANUAL REVISION 3.1
31
If Trane Trio then COMP C is on and COMP A and B are off.
If Trane Quad then COMP A is on and COMP B, C, and D are off.
SCROLL STEP 2 (37) Only with HVAC Software
6.2.43.
Only used with special patterns for Trane Trio and Quad compressors. These compressors provide
special staging as follows:
If Trane Trio then COMP A and B are on and COMP C is off.
If Trane Quad then COMP C and D are on and COMP A and B are off.
SCROLL STEP 3 (38) Only with HVAC Software
6.2.44.
Only used with special patterns for Trane Trio and Quad compressors. These compressors provide
special staging as follows:
If Trane Trio then COMP A, B, and C are on.
If Trane Quad then COMP B, C, and D are on and COMP A is off.
SCROLL STEP 4 (39) Only with HVAC Software
6.2.45.
Only used with special patterns for Trane Quad compressors. These compressors provide special staging
as follows:
If Trane Quad then COMP A, B, C, and D are on.